What your building needs, and when

Every check your Calgary building needs, how often, and who can do it. Print it and pin it up by the panel.

Which of these can I do myself?

Most of the quick monthly checks. The Alberta Fire Code lets an owner do the daily and monthly fire alarm checks once the service company has trained them. The rest needs a certified tech.

You you can do it   Tech needs a certified tech

Fire alarm

Every day
Look at the panel. Power on, no trouble lights. You
Every month
The short checks in CAN/ULC-S536. Your service company shows you how. You
Once a year
Every device in the building inspected and tested to CAN/ULC-S536, with a written report. Tech

Fire monitoring

Once a year
Signals sent to the monitoring station to prove they get there. Usually done with the fire alarm inspection. Tech
When people change
Update the monitoring company's call list so the right person gets the call. You

Sprinklers

Monthly or quarterly
Gauges and control valves checked. Valves open, pressure normal. Tech
Once a year
Full inspection and test to NFPA 25. Dry systems get a trip test before winter. Tech
Every 5 years
A look inside the pipes for rust and buildup. Tech

Backflow preventers

Once a year
Every testable device, to CSA B64.10.1. The City of Calgary requires it. Tech
After any repair
Tested again whenever a device is installed, repaired, cleaned or replaced. Tech
After every test
The tester files the result with the City. Ask for your copy. You

Fire extinguishers

Every month
On its hook, nothing in front of it, gauge in the green, pin in place. You
Once a year
Serviced and tagged to NFPA 10. Tech
Every 6 and 12 years
Most dry chemical units get opened up at 6 years and pressure tested at 12. Tech

Emergency lights and exit signs

Every month
Press the test button. Every light comes on, every exit sign is lit. You
Once a year
A full-length battery test, so the lights last as long as they're rated to. Tech

Private fire hydrants

Once a year
Opened, flushed and checked so it works when the fire department hooks up. Tech

Your records

Always
Reports, repair records and the logbook kept on site. The fire inspector can ask to see them. You
After every inspection
Get the failed items fixed. A report full of open problems doesn't make you compliant. You
SystemWhat gets checkedHow oftenWho does it
Fire alarmPanel shows normal power, no trouble lightsDailyOwner / staff
Short checks in CAN/ULC-S536MonthlyOwner / staff
Every device tested to CAN/ULC-S536, written reportYearlyCertified tech
Fire monitoringSignals sent to the monitoring station to prove they arriveYearlyCertified tech
Keep the monitoring company's call list currentWhen staff changeOwner / staff
SprinklersGauges and control valves checkedMonthly or quarterlyCertified tech
Full inspection and test to NFPA 25, dry systems trip testedYearlyCertified tech
Inside of pipes checked for rust and buildupEvery 5 yearsCertified tech
Backflow preventersEvery testable device tested to CSA B64.10.1YearlyCertified tech
Retest after any install, repair or replacementAs neededCertified tech
Get your copy of the report filed with the CityAfter each testOwner / staff
Fire extinguishersOn its hook, unblocked, gauge in the green, pin in placeMonthlyOwner / staff
Serviced and tagged to NFPA 10YearlyCertified tech
Internal check, then pressure test (most dry chemical)6 and 12 yearsCertified tech
Emergency lights and exit signsPress test: every light on, every sign litMonthlyOwner / staff
Full-length battery testYearlyCertified tech
Private hydrantsOpened, flushed and checkedYearlyCertified tech
RecordsReports, repair records and logbook kept on siteAlwaysOwner / staff
Every deficiency on the report fixedAfter each inspectionOwner / staff

Owner / staff: the building owner or someone they've chosen, once trained by the service company. Certified tech: a qualified technician, like Panther. A planning summary only. The Alberta Fire Code and the standards it names have the final say.

Panther Integration does all the certified tech checks on this list. Send us your last reports and we'll keep every date for your building. Call (587) 747-3810.

This is a summary to help you plan. The Alberta Fire Code and the standards it names have the final say, and your building may need more. Your last report should list what's due. If it doesn't, ask why.

We can keep track of it for you

Send us your last reports and we'll keep every date for your building. Call (587) 747-3810.

Call

Tell us about your building

Step 1 of 3

What kind of building is it?

We'll call to confirm the details. No pressure, no spam.