Common building problems, and what to do
It's 9 p.m. and the fire panel in the lobby won't stop beeping. Or a resident's fob suddenly says access denied. These are the problems Calgary building managers call us about most, with plain answers from our service calls.
Why is my fire alarm panel beeping?
A beep with a yellow trouble light isn't a fire. It means part of the system needs attention. The screen usually says what.
The panel is beeping and says trouble
Something on the system needs attention: a battery, a dirty detector, a wiring fault. Write down what the screen says and call us. We'll tell you if it can wait for a booked visit or needs someone today.
It says battery trouble or charger fault
Panel batteries wear out. We replace a lot of them after they fail the load test at the annual inspection. A charger fault can also mean the panel's power supply needs a look, so we check both.
It says ground fault
A wire somewhere on the system is touching ground. Usually we can trace it in the building's wiring. Once in a while the fault is a board inside the panel, and we bring in the manufacturer's tech.
It says a smoke detector is dirty
Detectors warn you when dust builds up, before they start causing false alarms. We replace the dirty one, and can check every detector in the building at once so you're not calling about them one at a time.
A panel on another floor has gone blank
In bigger buildings the main panel talks to other panels, often called nodes. If one loses power, the main panel shows it as missing. Treat it as urgent. That part of the building may not be protected.
A booster panel is showing trouble
Boosters power the horns and strobes on a floor or wing, and they have their own batteries. Those wear out too. We test and replace them. Fire alarm panel testing ›
Why does the fire alarm keep going off?
Most false alarms come from one device. Finding which one is the first job.
The alarm keeps going off and there's no fire
We pull the panel's history to see which device keeps setting it off, then work out why. We've traced false alarms to a recalled heat detector in a daycare kitchen, a rooftop duct detector full of rainwater, and dust from sweeping a parkade.
The fire department left, but the panel won't reset
Something is still in alarm, usually a detector that needs clearing or replacing. Call us. We find it, fix it and get the panel back to normal.
The fire department couldn't find which device went off
Many panels show the zone first, and a zone can be a whole floor. The exact device is one more button press away. We can show your staff how to find it, and tell you if your zone names send people to the wrong place.
Cooking keeps setting off the alarm
The panel history shows which detector it was. If it's the same one every time, we'll look at whether that's the right detector for that spot.
A smoke alarm is going off in a suite and nobody's home
A short chirp is usually a low battery. A full alarm in an empty suite needs checking. We've gone in after hours with a locksmith to make sure there was no fire before shutting it off.
We had a burst pipe and the panel is still in alarm
Water gets into detectors and other devices. We find which ones got wet, replace them and put the panel back to normal. Fire alarm inspection ›
What do I do about my inspection report?
A report with failures on it isn't unusual. What matters is getting them fixed and on record.
Our report has a list of failed devices
Each one should have its location on the report. We quote the repairs, and nothing gets done until you approve. Then we test again and update the report.
The fire department left a notice on our panel
That notice means the system needs repairs before it's back to normal. We fix what it lists and restore the system.
A pull station didn't work during the test
Sometimes the wiring is fine and the pull station itself has failed. We confirm which, replace it and test it again.
Some suites didn't let us in on inspection day
We come back for the suites we couldn't get into and update the report, so nothing is left untested.
I don't know what's due or when
Our free checklist lays out what each system needs and how often. Once you're with us, we track your due dates and reach out before they come up. Fire inspection checklist ›
Why is my monitoring company calling?
Monitoring is how a fire alarm reaches someone when nobody is in the building.
Monitoring says there's an unrestored trouble
Your panel sent a trouble signal and it hasn't cleared. We come out, find the cause and fix it, then confirm the signal has cleared with the monitoring station.
We're getting rid of our landline
Monitoring can run over a cell connection or the internet instead. It can also use one as a backup for the other.
What's the difference between passive and active communication?
Passive uses two paths, like a landline and a cell connection, and each sends a test signal on a schedule: every 6 hours for the main path and once a day for the backup. Active uses one path that's checked every few minutes.
Does our monitoring need to be ULC listed?
ULC listed monitoring is installed and monitored to CAN/ULC-S561 and S559. Some buildings must have it. Where it isn't required, non-ULC monitoring is an option. We'll tell you which one your building needs. ULC fire monitoring ›
What if the panel shows a sprinkler alarm?
Sprinkler alarms show up on the fire alarm panel, so they're often the first sign of a problem.
The panel shows a sprinkler flow alarm
Water is moving in the sprinkler pipes. A head may have gone off or a pipe may have broken. If there's fire, call 911. Then call our 24/7 line.
The fire department shut off a sprinkler valve
That part of the building is now out of service until the system is restored. Our emergency page explains what to do while it's out, and when you need a fire watch. 24/7 emergency help ›
Why did my emergency lights fail?
Emergency lights have one job: stay on when the power goes out. Batteries are usually what lets them down.
Most of our units failed the battery test
Usually it's old batteries. We replace them, test again and quote new units for any that still fail.
A stairwell has no emergency lights at all
We've found stairwells where the heads weren't connected to any battery unit. We add one and wire them in.
Remote heads keep burning out
That's often a wiring problem, not the bulbs. We trace it before replacing anything.
Some units are too high to test
Tell us before the visit. Units up in a warehouse ceiling need a lift and the right breakers marked. Emergency lighting ›
Why won't the door open with my fob?
Most door problems come down to the strike, the wiring or the software.
The front door won't unlock when it's really cold
Cold snaps freeze AC-powered door strikes. We get the door working, and can swap in a DC strike so it stops happening.
New residents get access denied at the intercom
Usually the system's database didn't update, or the entry panel and the access system don't match. We find which and fix it.
We can't add fobs from the office computer
The controllers have stopped talking to the computer. We get them back online, and tell you if they're old enough to start budgeting for new ones.
We need to know who let someone in
We pull the event report so you can see which fob or suite opened the door, and when. Access control ›
Why isn't my camera footage there?
You usually find out a camera's down when you need the footage.
A camera has been offline for days
Sometimes it's a setting. Sometimes a cable run is broken and has to be pulled again. We find out which.
Headlights wash out the parkade camera
Wide dynamic range cameras handle bright headlights and dark corners in the same shot.
A hard drive died and the footage went with it
We set up recorders with mirrored drives, so one failed drive doesn't lose anything. Video surveillance ›
Don't see your problem?
Call (587) 747-3810 and tell us what the panel or the door is doing. If it can't wait, our 24/7 line is always answered.